Contact
Uponor UK
Head Office
Uponor UK
The Pavillion
Blackmoor Lane
Watford Hertfordshiree
WD18 8GA

Uponor S-Press PLUS adapter wall penetr.

- For lead-through through walls.
- Dimensions of attachment plate (H x W x D) 100 x 50 x 2 mm.
- Hole circle diameter 33 mm.

Uponor S-Press PLUS adapter wall penetr.

Item details

1070652

Uponor S-Press PLUS adapter wall penetr. 16-G1/2"FT

Item available on request, minimum lead time 2 weeks
Uponor S-Press PLUS adapter wall penetr. 16-G1/2"FT

Documents

Product Information
259 B1142159

PI MLC tap water heating UK 1142159

Installation Report
116 B1120119

Installation Report MLC leak test report TW water (1120119)

Installation Report
127 B1120120

Installation Report MLC flushing protocol TW water (1120120)

Approval Certificate
262 B1095152

Uponor CER S-Press PLUS SYS MECH WRAS 1903901 GB (1095152)

About

Specification

- Unique press indicator
- Fast 3-step installation (press without bevel)
- Innovative QR code for immediate digital access
- Colour code
- Fixed press sleeve with insprection window
- Precise jaw fixation
- Fast diameter recognition
- Accurate test safety function
- 100% backward compatible with existing Uponor components
- Flow rate optimized fitting body

Application

-Heating systems (high temperature radiators) - where the water temperature does not continuously exceed 80ºC, 10 bar (Conditions to application Class 5 - BS EN ISO 21003-1:2008). The maximum short-term malfunction temperature is 100ºC for an accumulative 100 hours over the working life of the system. (Heating systems must be installed with room and water temperature controls in accordance with the current Building Regulations Parts L1 (Energy – Dwellings) and L2 (Energy – Non Dwellings) for England and Wales, or an equivalent national standard for Scotland or Republic of Ireland).

-Cold water domestic services: 0°C to 20°C where the water temperature does not exceed 20ºC, 16bar.

-Hot water domestic services: 20°C to 70°C where the water temperature does not continuously exceed 70ºC, 10 bar (Conditions to application Class 2 - BS EN ISO 21003-1:2008). The maximum short-term malfunction temperature is 95ºC for an accumulative 100 hours over the working life of the system.

-Uponor multilayer pipe can be used for DHW recirculating systems, provided the operating temperatures and pressures do not exceed the maximum conditions detailed under 'Domestic Services'

-Chilled water: -10°C to 10°C,10 bar. If risk of damage from freezing, a suitable anti-freeze additive must be used. Any additive must be suitable for use with Polyethylene, PPSU, EPDM and CW625N brass
if not different mentioned:

- Male and female threads acc.to EN 10226-1.

Certification

-WRAS : 1903901 - Uponor S-Press PLUS, S-Press PLUS, PPSU, MLC and SAC 16-32mm
-2101339 : Manifolds and adapters
-KIWA – UK water Regulation 4
-Manufacturing is in accordance with the international quality standard ISO 9001 and environmental standard ISO 14001.

Product drawings

1070652_LAB
1070652
78 B
1070652_REN
1070652
376 B
1070652_REN
1070652
113 B
1070652_ZMD
1070652
148 B