Uponor UK
Head Office
Uponor UK
The Pavillion
Blackmoor Lane
Watford Hertfordshiree
WD18 8GA

Uponor S-Press PLUS adapter swivel nut

- Made of tin-plated brass
- With fixed press sleeve, stop ring, pressed identification, colour code and test safety
- Press without bevel
- Releasable screw connector for 15mm cone
- Thread acc. to EN ISO 228-1.

Uponor S-Press PLUS adapter swivel nut

Item details

Uponor S-Press PLUS adapter swivel nut 16-G1/2"FT 15mm

Documents

Technical information
12 KB1142162

TI MLC tap water heating UK 1142162

Product Information
259 B1142159

PI MLC tap water heating UK 1142159

About

Specification

- Unique press indicator
- Fast 3-step installation (press without bevel)
- Innovative QR code for immediate digital access
- Colour code
- Fixed press sleeve with insprection window
- Precise jaw fixation
- Fast diameter recognition
- Accurate test safety function
- 100% backward compatible with existing Uponor components
- Flow rate optimized fitting body

Application

-Heating systems (high temperature radiators) - where the water temperature does not continuously exceed 80ºC, 10 bar (Conditions to application Class 5 - BS EN ISO 21003-1:2008). The maximum short-term malfunction temperature is 100ºC for an accumulative 100 hours over the working life of the system. (Heating systems must be installed with room and water temperature controls in accordance with the current Building Regulations Parts L1 (Energy – Dwellings) and L2 (Energy – Non Dwellings) for England and Wales, or an equivalent national standard for Scotland or Republic of Ireland).

-Cold water domestic services: 0°C to 20°C where the water temperature does not exceed 20ºC, 16bar.

-Hot water domestic services: 20°C to 70°C where the water temperature does not continuously exceed 70ºC, 10 bar (Conditions to application Class 2 - BS EN ISO 21003-1:2008). The maximum short-term malfunction temperature is 95ºC for an accumulative 100 hours over the working life of the system.

-Uponor multilayer pipe can be used for DHW recirculating systems, provided the operating temperatures and pressures do not exceed the maximum conditions detailed under 'Domestic Services'

-Chilled water: -10°C to 10°C,10 bar. If risk of damage from freezing, a suitable anti-freeze additive must be used. Any additive must be suitable for use with Polyethylene, PPSU, EPDM and CW625N brass
if not different mentioned:

- Male and female threads acc.to EN 10226-1.

Certification

-WRAS : 1903901 - Uponor S-Press PLUS, S-Press PLUS, PPSU, MLC and SAC 16-32mm
-2101339 : Manifolds and adapters
-KIWA – UK water Regulation 4
-Manufacturing is in accordance with the international quality standard ISO 9001 and environmental standard ISO 14001.

Product drawings

1141873_ZMD
1141873
194 B
1141873_REN
1141873
70 B