Uponor Smatrix Base PRO gateway module R-147 KNX
- connects a Uponor Smatrix Base PRO controller X-147 with a BMS or third-party KNX devices- power supply: 230VAC (+10%/-15%) / 50/60Hz- internal fuse: T5 F3.15AL 250V, 5x20 3.15A quick acting- operating temperature: 0°C ... +45°C- storage temperature: -20°C ... +70°C- max. consumption: 45W- power connection: 1m cable with europlug- connection terminals for system bus: 0.2mm² ... 1.5mm²- protection class: IP20 IIFunctions:- room temperatur from Uponor Base or third-party KNX thermostats- room setpoint from Uponor Base or third-party KNX thermostats- room relative humidity from Uponor Base or third-party KNX thermostats- room floor temperatur from Uponor Base or third-party KNX thermostats- actuator status from Uponor Base or third-party KNX system- foreced ECO from Uponor Base PRO or third-party KNX system- pump output from Uponor Base or third-party KNX system- boiler output from Uponor Base or third-party KNX system- heating/cooling curve settings/circuit from Uponor Move PRO to BMS or vice versa- heating/cooling modes from Uponor Base PRO to BMS or vice versaConsisting of:- gateway module R-147 KNX- power supply- mounting material (2 screws and 2 wall plugs)- quick guide
Item details
Documents
Technical manuals
EU declaration of conformity
Installation and Operation Manual Smatrix Base PRO R-147 KNX (1088247)
Uponor DoC Smatrix Base PRO 1087164 INT (1141505)
Application information
Specification
-autobalancing optimizing energy use and comfort-up to 6 room thermostats and 8 actuators (24V) per controller; 6 channel expansion module option (with M-140)-pump and boiler relays-valve and pump exerciseSmatrix Base Pro controller X-147 with optional touch screen I-147 and KNX option-up to 16 controller in one system-daisy chain wiring or star wiring (with M-141)-optional: display of controller information and settings (with I-147)-optional: BMS integration via KNX interface (with R-147 and I-147)Comfort settings comprises (with I-147)-temperature setback programs for each channel-max/min temperature limitations and relative humidity control-holiday settings and automatic summer/winter change-room bypass function-advance cooling settings and automatic summer/winter change-trend visualization (set point vs. room temperature, etc.)-accessories configuration-room check function and system diagnosticSmatrix Base Pro controller X-148 ModBus RTURead data points-temperature: outdoor / room / floor-humidity level-status of: actuator / pump / boiler / general purpose input (GPI)-connection status of thermostat-dynamic heat curve offset in integrated heat pumpRead and write data points-room setpoint-min/max levels for: setpoint / floor temperature-settings: comfort/eco and autobalancing on/off-heating/cooling: state / offset-cooling not allowed for a room-integrated heat pump defrost state
Application
- wired room temperature control for radiant heating and cooling- set point range: +5°C ... +35°C
Certification
- CE, EAC
Product drawings
Other
Rendered