Item details
Documents
Technical manuals
DGNB Declaration
Installation Report MLC leak test report TW water (1120119)
Installation Report MLC flushing protocol TW water (1120120)
Application information
Specification
- Oxygen diffusion resistant multi-layer composite pipe (PE-RT - adhesive – seamless aluminium/longitudinally welded aluminium - adhesive - PE-RT) produced using SACP and OWC-technology.- Fire classification E according to EN 13501-1.- With pipe end caps as hygienic seal according EN 806.
Application
- Tested/Approved according EN ISO 21003 Multilayer piping systems for hot and cold water installations inside buildings for application class 1,2,4,5/10bar- Tap water: The permanent operating temperature ranges from 0°C to 70°C at a maximum permanent operating pressure of 10 bar. The short-term malfunction temperature is 95°C for a period of 100 hours in the operating life time.- Heating: The permanent operating temperature ranges up to 80°C at a maximum permanent operating pressure of 10 bar. The short-term malfunction temperature is 100°C for a period of 100 hours in the operating life time.
Certification
- Approvals by local OM.E.g.- DVGW- AENOR
Product drawings
Z-drawing
Rendered
Label drawings