1 1/4" Pre-insulated Wirsbo hePEX with 1 1/2" insulation, 100-ft. coil
Part no.A6161250
Find a distributor
Availability of specific products varies by distributor.
Item details
Part information and details
Codes
Codes | IMC|UPC|IBC|IRC|NBC of Canada|IPC|UFGS|NPC of Canada|UMC|NSPC |
---|
Dimensions
Inner diameter coil [inch] | 27 inch |
---|---|
Outer diameter coil [inch] | 52.5 inch |
Coil width [inch] | 12 inch |
Inner diameter pipe [inch] | 1.054 inch |
Outer diameter pipe [inch] | 1.375 inch |
Weight per UOM [lbs/UOM] | 46.3 lbs/uom |
Listings
Listings | IAPMO-ES|ICC-ES-PMG|cNSFus-rfh|cNSFus-pw|CCMC|PPI TR-4|CSA|U.P.Code |
---|
Standards
Standards | ASTM F1960|ASTM F876|ASTM F2023|ASTM E814/ULC S115|ASTM F877|CSA B137.5|CSA B214|NSF/ANSI/CAN 61|NSF/ANSI 14 |
---|
Technical Data
Heat loss at dt=70°F [BTU/hr/ft] | 6.448 btu/hr/ft |
---|---|
Operating Pressure 1 [PSI] | 160 psi |
Operating Pressure 2 [PSI] | 100 psi |
Operating Pressure 3 [PSI] | 80 psi |
Operating Temperature 1 [°F] | 73 °F |
Operating Temperature 2 [°F] | 180 °F |
Operating Temperature 3 [°F] | 200 °F |
Linear expansion rate [inch/10°F/100ft] | 1.1 inch/10°f/100ft |
Material group | PEX |
Material Insulation | Polyethylene foam |
Pipe density [lb/ft³] | 0.0584 lb/ft³ |
R value | 9.04 |
Material Service Pipe | Crosslinked polyethylene (PEX-a) tubing; SDR-9, with EVOH oxygen barrier that conforms to DIN 4726 |
Thermal conductivity pipe [BTUin/ft²hrF°] | 0.22 btuin/ft²hrf° |